Multifamily HVAC System Comparison: Across Six Electrified Systems

A multi-story tan brick apartment building with retail stores, including Wegmans, on the ground floor. A blue car is parked on the street in front. The sky is partly cloudy.

If you ask three people, “Which HVAC system should we use?”

You may get three different answers.

We hear this question often from owners, engineers, and contractors trying to choose an electrified HVAC approach that won’t surprise them later, especially when it comes to first cost, maintenance costs, or energy use.

To help answer this question, we partnered with experts at Spectrum Energy to model six electrified HVAC options for a Maryland multifamily building to compare first cost, annual operating cost, and 15-year total cost using consistent assumptions.

The Six Electrified HVAC Systems 

PTHP

Packaged Terminal Heat Pump

SSHP Std

Standard Efficiency Split System Heat Pump

SSHP High

High Efficiency Split System Heat Pump

WSHP Std

Standard Efficiency Water Source Heat Pump

WSHP High

High Efficiency Water Source Heat Pump

VRF Air-Cooled

Air-Cooled Variable Refrigerant Flow

Methodology: Modeling inputs, exclusions, and financial assumptions are listed at the end. See methodology details

The goal isn’t to choose a universal winner; it is to make the trade-offs visible, so you can choose the system that best fits your building and ownership plan.

 

What drives 15-year total life-cycle cost?

You will see how installed cost, energy use, maintenance, and building ownership time affect each system differently, and small changes in inputs can shift results more than expected.

  • How long you expect to own the building and your maintenance plan.
  • For water source heat pump systems, central plant heating choice (electric boiler vs heat-pump boiler) can noticeably change total system life-cycle cost.
  • Higher efficiency did not always mean the lowest 15-year life-cycle cost.

 “The intent of this analysis was not to predict exact operating costs, but to compare systems on a consistent, apples-to-apples basis. By holding building geometry, loads, ventilation method and other building elements constant, the model highlights where HVAC system architecture and assumptions drive differences.”

— Jen Xiong, Energy Engineer III, Spectrum Energy

15-year Life Cycle Overview

The chart below compares a 15-year total life cycle cost across six electrified HVAC options using the same building and assumptions.

The three lowest outcomes are Split System Heat Pump (Standard efficiency) SSHP Std, Split System Heat Pump (High efficiency) SSHP high, and Variable Refrigerant Flow (Air-cooled) VRF Air-Cooled.

Bar chart compares total costs of different HVAC systems, with Baseline at $14.26M, PTHP at $12.03M, WSHP (Std) at $10.29M, and other systems ranging from $8.41M to $10.84M.

*15-year total cost (present value)

 

Across all six systems, the differences aren’t driven by a single variable.

First cost, energy performance, maintenance assumptions, and how long you plan to own the building, all interact differently depending on the system type. In this study, split-system heat pumps and air-cooled VRF produced the lowest 15-year total costs, while water-source systems improved materially when paired with different central plant assumptions. (shown later).

The insights below show where those differences come from and which assumptions matter most when applying the results to a real project.

 

Seven Key System Findings

 

1. Delivered first cost ranges show clear tiers

Delivered costs include equipment and installation for new construction ($/sq ft). Ventilation, plumbing, and rebates are not included.

Horizontal bar chart showing estimated and actual time spent on six tasks. Actual time exceeded estimated time for five out of six tasks, with Task 4 having the largest difference. 

Water-source heat pumps (WSHP) had the highest total cost. Split-system heat pumps and air-cooled VRF were closer to the middle. Packaged Terminal Heat Pumps (PTHP) can look like the budget option, but that depends on how many units you end up needing.

If you’re trying to keep costs down, start by comparing split systems vs. VRF. Consider WSHP only if your project is already set up to support the central plant approach.

In the modeled building, PTHP needed more units per apartment due to capacity limits, which increased installed costs.

First cost is heavily influenced by how many units you need to buy and install. Here’s what that looked like in this building.

 

2. PTHP “Unit Count” increased cost and maintenance

Each apartment needed roughly 2 tons of cooling capacity. The PTHP option was modeled at about 1.5 tons per unit, so this example required two PTHP units per apartment to meet capacity requirements. If you are considering PTHPs, confirm per-unit capacity and your apartment load early. Unit count drives equipment cost, installation labor, and future service calls.

In this study, we consulted with Davis Construction. They confirmed that from a construction and operations standpoint, unit count matters. Increasing units per apartment increases installation effort, coordination, and long-term service touchpoints, even if the equipment itself appears lower cost.
Bar chart comparing systems; PTHPs require two units per apartment, resulting in the highest unit count, while other systems require fewer units per apartment.

 

3. Utility rebates and first cost

Rebates can offset first cost, but they are a one-time event and program specific. We show them because they are useful for budgeting but not blended into the life cycle totals.

Bar chart comparing annual energy and maintenance costs for PTHP, showing costs with and without rebates: $361k/$587k for energy and $261k/$274k/$534k for maintenance over three groups.

VRF and SSHP High can outperform other options in rebate value. Base your decision on first cost minus rebates and life cycle cost, viewed side by side. Don’t blend them and hide the trade-offs.

These next two charts show modeled annual HVAC electricity cost for the same building.

 

4. Higher annual energy cost with electric boilers

Bar chart comparing energy costs per square foot for different options, showing a decrease from $0.49 to $0.37 as efficiency increases; baseline is $0.57. Construction and energy costs shown below.

This chart shows modeled annual HVAC electricity cost when the WSHP options use an electric boiler at the central plant. In this scenario, VRF has the lowest annual electricity cost, and both split system options perform well.

The key takeaway is that WSHP energy cost is sensitive to the central plant heating choice, and an electric boiler pushes the WSHP results higher in this model.

With an electric boiler, WSHP energy cost is higher in this study.

 

5. Lower annual energy cost with heat pump boilers

Bar chart comparing energy costs per square foot for different options, showing a decrease from $0.49 to $0.37 as efficiency increases; baseline is $0.57. Construction and energy costs shown below.

This chart shows the same building and the same assumptions, but the WSHP options are paired with a heat pump boiler instead of an electric boiler. Notice what changes. The split system and VRF results stay essentially the same, but both WSHP options cost drops. The takeaway is that the central plant heating choice is part of the WSHP system decision and it can change the outcome.

With a heat pump boiler, WSHP energy cost drops and becomes more competitive in this study.

“For systems that rely on a central plant, the plant configuration is part of the system choice. Changing the boiler assumption materially changes the WSHP results in this study, which is why those decisions should be evaluated together rather than in isolation.”

— Jen Xiong, Energy Engineer III, Spectrum Energy

Bar chart comparing median home values: U.S. overall $339k, Texas and Houston $215k, Mansfield and Fort Worth $249k, and Arlington $210k as of August 2023.

6. Maintenance costs reflect service type

Maintenance values reflect manufacturer-recommended service activities for this modeled building and are shown for comparison. Recalculate using your staffing and service approach before applying to a project.

“To keep systems fair in comparison, we included manufacturer-recommended maintenance and costs of a certified technician to perform all maintenance work. Most people do not have a technician going to evaluate and look at the operation of each unit once a year. That usually doesn’t happen. Usually, in residential and/or multifamily buildings, maintenance is limited to filter changes only.”

— Tim Dorman, Innovative Solutions Director, Havtech

In this study, because PTHPs were modeled as two units per apartment, it increased the number of filters, inspections, and service touches the building has to manage. The model also assumed multiple filter changes plus an annual checkup per unit, which may be more than how some portfolios maintain PTHPs in practice.

Treat this chart as a planning range, then check it against how you perform maintenance:

  • Are filters changed by in-house technicians or through a 3rd party?
  • Do you change “filters-only” most years, or do full inspections on a set schedule?

Those choices affect the outcome more than people expect, and they’re specific to your staffing model and service standards.

Maintenance is what you staff for and manage through service calls.

Now, looking back to the 15-year total cost example, ownership horizon and replacement timing can change how these annual differences add up.

 

7. Fifteen-year total cost varies across systems

Bar chart compares total costs of different HVAC systems, with Baseline at $14.26M, PTHP at $12.03M, WSHP (Std) at $10.29M, and other systems ranging from $8.41M to $10.84M.

The lowest 15-year total life cycle costs are SSHP High, SSHP Std, and air-cooled VRF.

A 15-year view aligns with many ownership plans, but it is still a snapshot. If you expect a longer ownership period, equipment replacement timing can become a larger part of the decision and should be evaluated separately.

Our HVAC equipment lifespan planning ranges help you check replacement timing when you are evaluating holding your building longer than 15 years. 

Check out our HVAC equipment lifespan planning ranges

These totals help you compare systems. The right answer depends on how long you’ll own the building and what you assume for replacements.

“These results are best used as a comparison framework. Actual project outcomes depend on whole building designs, utility rates, service practices, and ownership strategy, which is why we encourage teams to re-run the assumptions for their specific context.”

— Jen Xiong, Energy Engineer III, Spectrum Energy

Choosing the Right System

✅ Best fit    🟦 Situational    🟧 Not a primary fit

Your Concern

PTHP

SSHP (Std)

SSHP (High)

WSHP (Std)

WSHP (High)

VRF
(Air-Cooled)

Minimize 15-year total cost

🟧

🟧

🟧

Cut yearly HVAC electric bills

🟧

🟦

🟦

Avoid central plant ‘it depends’ variables

🟦

🟧

🟧

Biggest improvement if the central plant gets more efficient

🟧

🟧

🟧

🟧

Quickest to repair or swap out

🟦

🟦

🟧

🟧

🟦

*Comparison based on study assumptions.

No option “wins” in every scenario. The best-fit depends on how long you plan to own the building, who pays the utility bills, how the system will be serviced day-to-day, and (for water-source systems) the central plant concept you’re operating.

Before applying these results to your building, keep three things in mind:

  • How long you plan to own the building. Shorter holds favor lower first cost. Longer holds reward lower operating costs.
  • Who pays utilities. If the owner-pays, efficiency savings matter more.
  • For water-source systems, the central plant is part of the system. Plant assumptions can noticeably change outcomes.

If these match your situation, the results should translate well. If not, the rankings may shift.


Request an HVAC Planning Call

Get a System Fit Assessment

About the author
Tim Dorman is the Innovative Solutions Director at Havtech. He brings deep expertise in Indoor Environmental Quality and HVAC system design, helping clients implement smarter, more efficient mechanical solutions. Known for his collaborative approach and technical insight, Tim is a trusted advisor across the building industry. 
Tim Dorman

Tim Dorman

Innovative Solutions Director, Havtech

Gratitude

A sincere thank you to Spectrum Energy for the many hours of research, modeling and analysis that made this study possible.

We also want to recognize the project partners and subject matter experts who reviewed assumptions, pressure-tested outputs, and helped ensure the findings are practical for real multifamily projects, including Davis Construction and other contributors who supported the work.

 

  • Modeled Building:
    • 452 apartments
    • 355,000 residential sq. ft.
    • Each apartment is modeled at roughly two tons.
  • Loads:
    • All systems except VRF: peak-load of 577-ton
    • VRF: 451-ton block load
    • Room neutral ventilation 32,000 cu. ft. per min. (constant across scenarios)
  • Climate / Geography: Washington, DC Typical Meteorological Year, version 3 weather dataset
  • Baseline / comparison logic: ASHRAE 90.1-2019 Energy Cost Budget (ECB)
  • Energy rate assumption: $0.13 per kilowatt-hour
  • First cost definition:
    • New construction
    • Delivered cost expressed as $/sq. ft. includes equipment + install
    • Equipment-only expressed as $/ton. (Electrical included)
  • Exclusions: HVAC system costs shown exclude ventilation (Dedicated Outdoor Air System), and plumbing (as stated during capital cost framing).
  • Rebates: Utility rebates are shown separately as a budgeting input. They are one-time incentives and not included in the 15-year total cost.
  • Limitations: Study is a “snapshot in time.” Havtech does not guarantee any project will match these numbers. The purpose is to compare values.
  • Utility baseline: (ASHRAE 90.1-19 ECB PTHP)

Modeled by Spectrum Energy using consistent assumptions across six electrified options for a Maryland multifamily case study building.

Financial Assumptions Behind the 15-Year Totals

  • Energy escalation: 3.0%
  • Maintenance escalation: 5.0%
  • Discount rate: 4.2%
  • Inflation rate: 4.2%
  • 15-Year Total Cost (Present Value, discounted at 4.2%)

News & Updates from HavTech

Stay Up to Date

Tap into practical resources built by people who know what it takes to keep systems performing.

View All News

The logo features two red concentric circles with "VAN-PACKER®" in red and "CO." in black, all in bold capital letters, centered on a white background.

Van-Packer is a leading manufacturer of factory-built grease duct systems for commercial kitchen applications, known for their safety, performance, and code compliance. Through this new…

Fast Answers. Full Support. Real Results.

Get expert guidance, responsive service, and the confidence that your HVAC system is built to perform.

Talk to an HVAC Specialist