How A2L Refrigerants Change VRF Design in Hotels and Multifamily Buildings

Several large Daikin outdoor air conditioning units, part of A2L VRF systems in hotels and multifamily buildings, are lined up next to a building on a sunny day.

A2L refrigerants didn’t remove Variable Refrigerant Flow (VRF) as an equipment option in hotels and multifamily buildings. 

But they did change one of the first refrigerant safety checks engineers perform. 

Instead of comparing total system charge to the smallest room, engineers now have to evaluate how much refrigerant could be released into the space. 

That includes: 

  • The actual layout 
  • The smallest occupied spaces 
  • What qualifies as a connected space 
  • The amount of refrigerant that could be released into the room 

It’s no longer just about ASHRAE 15 and ASHRAE 34.

Local code adoption, UL 60335-2-40, and how those standards are currently interpreted influence whether the design is effective. 

This article highlights key insights shared by Chris Bellshaw of Daikin Comfort Technologies North America, Inc., on how A2L is changing early VRF design in multifamily and hospitality applications. 

“A2L didn’t make VRF unworkable. It made simple early design checks unworkable.”

Chris Bellshaw, VP of Commercial Strategy and Business Development for Daikin Comfort Technologies North America, Inc.


Start with a VRF Layout vs. a Refrigerant Check 

A refrigerant safety review starts with a layout. Locate indoor and outdoor units, estimate piping paths, identify branch or changeover box locations, and define the occupied and enclosed spaces that shape the next steps.

VRF System Layout  Diagram of an office floor plan showing multiple ceiling-mounted air conditioning units connected by blue and red lines to two HVAC controllers, illustrating an A2L VRF system design commonly used in hotels and multifamily buildings.

Example VRF system layout showing outdoor units, refrigerant piping network, and indoor units serving multiple spaces. A preliminary layout helps evaluate refrigerant distribution, room conditions, and areas that may need closer review. Source: Daikin Comfort Technologies North America, Inc. 

In the layout, identify: 

  • Indoor unit types and locations 
  • Outdoor unit selection 
  • Approximate piping lengths 
  • Branch or changeover box locations 
  • A first-pass refrigerant charge estimate 
  • Enclosed and occupied spaces that need review 

Once the layout is ready, the next step is to evaluate the Effective Dispersal Volume Charge (EDVC), Maximum Releasable Refrigerant Charge (MREL), connected spaces, and corridor conditions in the right order. 

A typical design sequence looks like this: 

  1. Lay out the system
  2. Identify occupied and enclosed spaces (start with the smallest room)
  3. Calculate the EDVC
  4. Calculate the MREL
  5. Then evaluate connected spaces and corridor conditions

Understanding EDVC and MREL in A2L VRF Design 

The next step is to evaluate EDVC and MREL. 

  • EDVC defines what the room can safely handle. 
  • MREL defines what the system could release into that space. 
Get more details in the A2L VRF webinar. 

Walkthrough the design checks, room calculations, and design coordination of A2L VRF design. Earn PDH credit.

 Download the webinar replay


How to Evaluate VRF Refrigerant Charge Limits 

Now verify the system complies with the refrigerant safety limits defined in ASHRAE 15.

ASHRAE 15 now allows mitigation controls that can limit how much refrigerant is released into the space, which directly affects how MREL is evaluated.

 

Step 1: Calculate the effective dispersal volume charge (EDVC)

The EDVC calculation determines how much refrigerant can safely disperse within an occupied or connected space.

 

Spaces Evaluated for Refrigerant Safety

Diagram showing air flow from an outdoor unit to three enclosed, occupied spaces; only spaces with ventilation or refrigeration systems, as seen in A2L VRF system design in hotels and multifamily buildings, are checked as acceptable.

Only enclosed, occupied spaces served by the VRF system are evaluated when determining refrigerant safety limits. Spaces that are not conditioned or do not contain refrigerant piping are typically excluded. Source: Daikin Comfort Technologies North America, Inc.

 

Effective Dispersal Volume Charge (EDVC) formula:

EDVC = Veff × LFL × CF × Focc

  • Veff = effective dispersal volume of the space
  • LFL = lower flammability limit of the refrigerant
  • CF = concentration factor
  • Focc = occupancy adjustment factor

This means the allowable refrigerant charge is based on the actual volume of the space being evaluated.

  • A single room
  • Multiple connected rooms
  • Corridor ceiling plenum
  • Another enclosed zone connected by airflow

Identifying the smallest occupied space early in design is important.

 

Step 2: Calculate the maximum releasable refrigerant charge (MREL)

MREL represents the portion of refrigerant that could enter a space during a leak before mitigation control takes effect.

The MREL calculation typically includes:

  • Refrigerant in downstream piping
  • Refrigerant inside the indoor unit heat exchanger
  • Refrigerant released before safety shutoff valves close
  • Piping length and diameter near the leak location

 Maximum Releasable Refrigerant Charge (MREL) formula:

Refrigerant contained in the indoor unit coil and downstream piping up to the shutoff valve
+
Additional refrigerant released during the shutoff valve closure delay

*In many VRF design examples, the valve-closure release is approximated at about 0.279 lb per SSOV, depending on system assumptions.

Diagram showing an A2L VRF system design in hotels and multifamily buildings, highlighting refrigerant sensors, safety shut off valves, and indoor unit leak detection relative to occupied space and SSOV shutdown.

A2L VRF design focuses on releasable charge, not total system charge. Integrated leak detection and safety shutoff valves limit how much refrigerant can enter an occupied space, allowing engineers to evaluate compliance based on MREL versus EDVC. Source: Daikin Comfort Technologies North America, Inc.

 

In modern A2L VRF design, mitigation controls such as refrigerant sensors and safety shutoff valves can significantly reduce the amount of refrigerant that could enter a space.

That’s why MREL is often much smaller than the total system charge.

 

Step 3: Compare MREL to EDVC

As a final confirmation, compare MREL to EDVC.

If MREL ≤ EDVC = the system complies
If MREL > EDVC = mitigation or redesign is required

When the releasable charge exceeds the allowable dispersal volume, engineers typically resolve the issue by adjusting the design. Options include:

  • Relocating branch selector boxes
  • Reducing piping volume in the evaluated space
  • Using connected-space calculations
  • Adding mitigation controls such as leak detection or shutoff valves

Once that relationship is verified, start evaluating small rooms, connected spaces, and corridor ceiling conditions throughout the system.

 A flowchart outlining A2L VRF design steps: 1. Layout, 2. Evaluate the smallest room for EDVC and MREL, 3. Work outward to system conditions.


How to Evaluate Small Rooms in A2L VRF Systems

Small rooms are still the first stress test in A2L VRF design because they often determine whether a system complies with refrigerant safety limits.

 

Small hotel and apartment room example

Consider a room that is 112 square feet with an 8.5-foot ceiling.

The maximum amount of refrigerant that could be released into that room is just over 9 pounds. At the indoor unit branch, assuming long piping, the maximum releasable charge is much lower at approximately 2.78 pounds.

In this case, most of the releasable charge comes from the piping, not the indoor unit. That is why piping length and branch location directly affect the calculation.

Do Bathrooms Count Toward VRF Room Volume?

Bathrooms only count if they function as a connected space.

If the bathroom has a closable door and no meaningful airflow path (no transfer grille or sufficient door undercut), it should not be included.

If there is a clear airflow path, it can be included.

Do not include the bathroom just to increase allowable volume. Include it only when the connected-space logic is real and defensible.

 

Diagram showing airflow from an outdoor unit (ODU) to two indoor spaces, illustrating A2L VRF system design in hotels and multifamily buildings; the middle unconditioned space is labeled "N/A, Unconditioned, No exposed pipe.

In A2L VRF design, evaluate the smallest enclosed space served by the system when checking refrigerant charge limits. Source: Daikin Comfort Technologies North America, Inc.


Using Connected Spaces to Increase Allowable Refrigerant Volume

How connected spaces are defined plays a major role in A2L VRF design. When rooms are connected by airflow, they can be evaluated as a single volume instead of separate spaces.

This can significantly increase the allowable refrigerant charge compared to evaluating each room individually.

 

When can multiple rooms be evaluated together?

A small room may not meet refrigerant safety limits when evaluated on its own. But if it is connected to adjacent spaces through airflow paths, those spaces can be evaluated together.

When that connection is valid, the effective dispersal volume increases while the maximum releasable charge remains unchanged.

Connected space calculations typically apply when multiple rooms share:

  • Common supply or return ductwork
  • An open ceiling plenum
  • A transfer path that allows air to circulate between spaces

In many VRF systems, there are no dampers or controls isolating these zones. As a result, the spaces can often be evaluated as a single volume.

The key requirement is that the connection is real. Air must be able to move between spaces without dampers, barriers, or closed partitions that isolate the room.

If airflow is restricted, the spaces must be evaluated separately.

Corridor Ceilings and Branch Selector Boxes in VRF Design

When refrigerant piping or branch selector boxes are located above corridor ceilings, that plenum may become the space used for refrigerant dispersion calculations.

This is where many otherwise workable designs become more complex.

 

Evaluating Refrigerant Release in a Corridor Ceiling Plenum

Diagram of a building floor with three rooms, HVAC system components, air ducts, restroom, and green arrows indicating length and height measurements—ideal for illustrating A2L VRF system design in hotels and multifamily buildings.

Corridor ceiling plenums often contain VRF piping and branch selector boxes. When evaluating A2L refrigerant safety limits, engineers may need to treat this ceiling volume as the dispersal space for a potential refrigerant leak. Source: Daikin Comfort Technologies North America, Inc.

Some aspects of the current standards are interpreted more conservatively than many engineers would prefer, particularly around releasable charge and evaluated spaces. But as Chris Bellshaw pointed out, the practical approach is to design around the interpretation that the project must comply with.

“The industry may not agree with the current interpretation, but it’s the way the standard is written, and that is how teams have to design today.”

Chris Bellshaw, Vice President of Commercial Strategy and Business Development for Daikin Comfort Technologies North America, Inc.

From a design review standpoint, the biggest coordination issues usually show up in corridor devices and branch-selector placement, not in the room itself.

 

Mitigation strategies for VRF design

When branch selector boxes are located above corridor ceilings, engineers usually work through a few options:

  1. Use available volume in the ceiling or adjacent space
    In some cases, the local ceiling zone or an adjacent open area provides enough volume to accommodate the releasable charge.
  2. Evaluate connected spaces
    If the corridor plenum is connected to adjacent spaces, the effective dispersal volume may extend beyond the local ceiling zone. This depends on having a real, defensible airflow path.
  1. Use a secondary enclosure with on-demand ventilation
    When the available volume is limited, an enclosure around the branch selector box can provide a controlled mitigation approach.

Natural or mechanical ventilation may also be considered, but in practice, these approaches are often less practical than using available volume, connected spaces, or a dedicated enclosure.

 

Typical VRF System Layout in Multifamily or Hotel Buildings

Diagram of a building elevation illustrating A2L VRF system design in hotels and multifamily buildings, featuring a VRF pipe shaft, floor corridors with branch selectors, rooms with indoor units, refrigerant sensors, and safety shutoff valves.

In many multifamily and hotel buildings, branch selector boxes and refrigerant piping are in corridor ceilings adjacent to occupied rooms. These locations influence how refrigerant safety limits are evaluated. Source: Daikin Comfort Technologies North America, Inc.

Changeover and branch selector boxes are often evaluated more conservatively than expected. 

“Follow the interpretation the project has to live with, then design around it.”

 Chris Bellshaw, Vice President of Commercial Strategy and Business Development for Daikin Comfort Technologies North America, Inc.

That shifts the design question. It is no longer just about corridor volume. It is about which compliance path the layout can support.


What to Verify Before A2L VRF Design Development

Confirm the conditions that affect refrigerant charge calculations:

  • Smallest occupied rooms and their usable volume
  • Whether bathrooms should be included in room volume
  • Branch selector and changeover box locations
  • Whether common areas qualify as connected spaces
  • Piping lengths that influence releasable charge
  • Corridor strategy: local volume, connected space, or enclosure
  • How pipe chases and shafts are treated in the drawings and specifications

These checks often determine whether a design complies before detailed calculations begin. Verifying them early can prevent rework later in design.

 

Review Your A2L VRF Design

About the author
Tim Dorman is the Innovative Solutions Director at Havtech. He brings deep expertise in Indoor Environmental Quality and HVAC system design, helping clients implement smarter, more efficient mechanical solutions. Known for his collaborative approach and technical insight, Tim is a trusted advisor across the building industry. Tim Dorman is the Innovative Solutions Director at Havtech. He brings deep expertise in Indoor Environmental Quality and HVAC system design, helping clients implement smarter, more efficient mechanical solutions. Known for his collaborative approach and technical insight, Tim is a trusted advisor across the building industry.
Tim Dorman

Tim Dorman

Innovative Solutions Director
Havtech


Technical Contributor
Chris Bellshaw serves as the Vice President of Commercial Strategy and Business Development for Daikin Comfort Technologies North America, Inc., bringing over 30 years of expertise in the HVAC and VRV/VRF industry. His career began in the UK as an HVAC design-build contractor, gaining experience in all commercial HVAC systems including VRV/VRF.
Chris Bellshaw 2

Chris Bellshaw

VP of Commercial Strategy & Business Development
Daikin Comfort Technologies

News & Updates from HavTech

Stay Up to Date

Tap into practical resources built by people who know what it takes to keep systems performing.

View All News

Fast Answers. Full Support. Real Results.

Get expert guidance, responsive service, and the confidence that your HVAC system is built to perform.

Talk to an HVAC Specialist